Operating Instructions

6.20 Cascade control
Overview
The cascade control is ideal for applications in which, for example, significantly fluctuating
pressures or flow rates are equalized.
3
'21&
'212
'2&20
'21&

'212
'212

'2&20
'2&20
9287
 *1'
...
...
S
 U
S
 U
S
 U
0 0 0 '0
DM Speed-controlled motor
M1 … M3 Uncontrolled motors
P Pressure sensor. Interconnect the signal of the pressure sensor with the actual-value input
of the technology controller.
Figure 6-39 Example: Cascade control for the pressure in a liquid pipe
To deploy the cascade control, you must activate the technology controller.
Depending on the set-actual variance of the technology controller, the cascade control of the
inverter switches a maximum of three additional motors directly to the line supply via contactors.
3,'
Advanced commissioning
6.20 Cascade control
Converter with the CU230P-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257946B AF 295