Operating Instructions
List of Parameters
Parameters
1-343
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Sets the switch on time in hours and minutes for time switch 2 (DTC2).
BO: r8423 = 1 signal:
The condition for the set weekday (p8420) and switch-on time has been fulfilled.
Index: [0] = Hour (0 ... 23)
[1] = Minute (0 ... 59)
Dependency: Refer to: p8409, p8420, r8423
Notice: This parameter can only be changed when p8409 = 0.
Note: DTC: Digital Time Clock (timer)
RTC: Real-time clock
Description: Sets the switch off time in hours and minutes for time switch 2 (DTC2).
BO: r8423 = 0 signal:
The condition for the set weekday (p8420) and switch-off time has been fulfilled.
Index: [0] = Hour (0 ... 23)
[1] = Minute (0 ... 59)
Dependency: Refer to: p8409, p8420, r8423
Notice: This parameter can only be changed when p8409 = 0.
Note: DTC: Digital Time Clock (timer)
RTC: Real-time clock
Description: Display and binector output for the output of timer 2 (DTC2).
Where a weekday is de-activated, the following applies (p8420):
- The binector output for this timer is inactive (r8423.0 = 0).
Where a weekday is activated, the following applies (p8420):
- The ON/OFF time setting (p8421, p8422) for this timer has an instant effect on the binector output (r8423).
Dependency: Refer to: p8409, p8420, p8421, p8422
Notice: This parameter can only be changed when p8409 = 0.
Note: DTC: Digital Time Clock (timer)
RTC: Real-time clock
p8421[0...1] RTC DTC2 switch-on time / RTC DTC2 t_ON
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 59 0
p8422[0...1] RTC DTC2 off time / RTC DTC2 t_OFF
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 59 0
r8423.0...1 BO: RTC DTC2 output / RTC DTC2 output
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Timer on Yes No -
01 Timer ON negated No Yes -