Operating Instructions

List of Parameters
Parameters
1-297
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Sets the value for fixed value 15 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description: Selects the method that can be used to select the fixed setpoints.
Value: 1: Fixed value selection direct
2: Fixed value selection binary
Description: Sets the signal source to select the fixed value of the technology controller.
Dependency: Refer to: p2221, p2222, p2223
Description: Sets the signal source to select the fixed value of the technology controller.
Dependency: Refer to: p2220, p2222, p2223
Description: Sets the signal source to select the fixed value of the technology controller.
Dependency: Refer to: p2220, p2221, p2223
p2215[0...n] CO: Technology controller, fixed value 15 / Tec_ctr fix val 15
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: DDS, p0180
Units group: 9_1 Unit selection: p0595
Min Max Factory setting
-200.00 [%] 200.00 [%] 150.00 [%]
p2216[0...n] Technology controller fixed value selection method / Tec_ctr FixVal sel
Access level: 2 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
1 2 1
p2220[0...n] BI: Technology controller fixed value selection bit 0 / Tec_ctrl sel bit 0
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0
p2221[0...n] BI: Technology controller fixed value selection bit 1 / Tec_ctrl sel bit 1
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0
p2222[0...n] BI: Technology controller fixed value selection bit 2 / Tec_ctrl sel bit 2
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0