Operating Instructions
Parameters
List of parameters
1-312
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Note: ESM: Essential Service Mode
Permissible signal sources:
- BO: r0722.x (high active)
- BO: r0723.x (low active), x = 0 ... 5, 11, 12
Description: Sets the setpoint source for essential service mode (ESM).
Value: 0: Last known setpoint (r1078 smoothed)
1: Fixed speed setpoint 15 (p1015)
2: Control Unit analog input 0 (AI 0, r0755[0])
3: Fieldbus
4: Technology controller
6: Enable the response OFF1
7: Enable the response OFF2
Warning: Re p3881 = 4:
If the technology controller is used as setpoint source, then this must first be configured. p2251 must be set to 0.
Note: ESM: Essential Service Mode
When the essential service mode is activated, the effective speed setpoint is displayed in r1114.
Re p3881 = 0:
The last known setpoint value is only transmitted safely if it was present consistently for at least 30 s prior to activat-
ing the essential service mode. If this condition is not met, fixed speed setpoint 15 (p1015) is used.
Re p3881 = 6:
n_act = 0: pulse cancellation and switching-on inhibited.
n_active > 0: braking along the ramp-function generator down ramp (p1121), pulse cancellation and switching-on
inhibited.
Re p3881 = 7:
n_act = 0: pulse cancellation and switching-on inhibited.
n_act > 0: immediate pulse cancellation and switching-on inhibited.
Description: Sets the alternative setpoint source for essential service mode (ESM).
This setpoint is used when the setpoint source set in p3881 is lost.
Value: 0: Last known setpoint (r1078 smoothed)
1: Fixed speed setpoint 15 (p1015)
2: Maximum speed (p1082)
Dependency: Refer to: p3881
Note: ESM: Essential Service Mode
The alternative setpoint source is only active for p3881 = 2, 3, 4.
p3881 ESM setpoint source / ESM setp_src
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7033
Min Max Factory setting
0 7 0
p3882 ESM setpoint source alternative / ESM setp_src alt
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7033
Min Max Factory setting
0 2 0