Operating Instructions

SINAMICS G120 CU230P-2 Control Units
List Manual (LH9), 04/2014, A5E33838102B AA
43
2 Parameters
2.2 List of parameters
Description: Displays the actual speed setpoint at the input of the speed controller or U/f characteristic (after the interpolator).
Dependency: Refer to: r0020
Note: The speed setpoint is available smoothed (r0020) and unsmoothed (r0060).
Description: Display and connector output for the speed setpoint after the setpoint filters.
Description: Displays the actual speed of the closed-loop speed control and the U/f control.
For U/f control and when slip compensation is deactivated (see p1335), the synchronous speed to the output
frequency is shown in r0063[0].
Index: [0] = Unsmoothed
[1] = Smoothed with p0045
[2] = Calculated from f_set - f_slip
Dependency: Refer to: r0021, r0022
Note: The speed actual value r0063[0] is additionally displayed - smoothed with p0045 - in r0063[1].
The speed (r0063[2]) calculated from the output frequency and slip can only be compared with the speed actual
value (r0063[0]) in the steady-state.
Description: Displays the actual system deviation of the speed controller.
Description: Displays the slip frequency for induction motors (ASM).
r0060 CO: Speed setpoint before the setpoint filter / n_set before filt.
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 3_1 Unit selection: p0505 Func. diagram: 2701, 2704, 5020,
6030, 6799
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
r0062 CO: Speed setpoint after the filter / n_set after filter
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 3_1 Unit selection: p0505 Func. diagram: 6020, 6030, 6031
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
r0063[0...2] CO: Speed actual value / n_act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 3_1 Unit selection: p0505 Func. diagram: 6020, 6799
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
r0064 CO: Speed controller system deviation / n_ctrl system dev
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 3_1 Unit selection: p0505 Func. diagram: 5040, 6040
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
r0065 Slip frequency / f_Slip
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 2_1 Unit selection: p0505 Func. diagram: 6310, 6700, 6727,
6730, 6732
Min Max Factory setting
- [Hz] - [Hz] - [Hz]