Operating Instructions
SINAMICS G120 CU230P-2 Control Units
List Manual (LH9), 04/2014, A5E33838102B AA
145
2 Parameters
2.2 List of parameters
Description: Sets the signal source for the speed/velocity limit of the negative direction.
Description: Sets skip speed 1.
Dependency: Refer to: p1092, p1093, p1094, p1101
Notice: Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
Note: The skip (suppression) speeds can be used to prevent the effects of mechanical resonance.
Description: Sets skip speed 2.
Dependency: Refer to: p1091, p1093, p1094, p1101
Notice: Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
Description: Sets skip speed 3.
Dependency: Refer to: p1091, p1092, p1094, p1101
Notice: Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
Description: Sets skip speed 4.
Dependency: Refer to: p1091, p1092, p1093, p1101
Notice: Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
p1088[0...n] CI: Speed limit in negative direction of rotation / n_limit neg
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2000 Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 3050
Min Max Factory setting
- - 1086[0]
p1091[0...n] Skip speed 1 / n_skip 1
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: p2000 Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: 3050
Min Max Factory setting
0.000 [rpm] 210000.000 [rpm] 0.000 [rpm]
p1092[0...n] Skip speed 2 / n_skip 2
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: p2000 Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: 3050
Min Max Factory setting
0.000 [rpm] 210000.000 [rpm] 0.000 [rpm]
p1093[0...n] Skip speed 3 / n_skip 3
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: p2000 Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: 3050
Min Max Factory setting
0.000 [rpm] 210000.000 [rpm] 0.000 [rpm]
p1094[0...n] Skip speed 4 / n_skip 4
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: p2000 Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: 3050
Min Max Factory setting
0.000 [rpm] 210000.000 [rpm] 0.000 [rpm]