Operating Instructions
2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
58 List Manual, 04/2018, A5E33838102
Description: Displays the power unit fan operating hours.
The number of hours operated can only be reset to 0 in this parameter (e.g. after a fan has been replaced).
Dependency: Refer to: p0252
Refer to: A30042
Note: For liquid-cooled chassis power units, the operating hours of the inner fan are displayed in p0251 and not in p0254.
Description: Sets the maximum operating time of the power unit fan.
The prealarm (warning) is output 500 hours before this set value.
The monitoring is deactivated with p0252 = 0.
Dependency: Refer to: p0251
Refer to: A30042
Note: For PM330 power units, the maximum operating time of the fan on the power unit is saved and displayed in p0252.
The "Restore factory setting" function or a project download does not influence p0252. Users can manually change
the maximum operating time of the fan. The modified value is also saved to the power unit.
Description: Displays the power unit fan operating hours of the internal fan in the power unit.
The number of hours operated can only be reset to 0 in this parameter (e.g. after a fan has been replaced).
Dependency: Refer to: A30042
Note: For liquid-cooled chassis power units, the operating hours of the inner fan are displayed in p0251 and not in p0254.
Description: Sets the shutdown thresholds for the ground fault monitoring.
The setting is made as a percentage of the maximum current of the power unit (r0209).
Index: [0] = Threshold at which precharging starts
[1] = Threshold at which precharging stops
Dependency: Refer to: p1901
Refer to: F30021
Note: This parameter is only relevant for chassis power units.
p0251[0...n] Operating hours counter power unit fan / PU fan t_oper
PM330 Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: PDS, p0120
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 [h] 4294967295 [h] 0 [h]
p0252 Maximum operating time power unit fan / PU fan t_oper max
PM330 Access level: 4 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 [h] 100000 [h] 40000 [h]
p0254[0...n] Operating hours counter power unit fan inside the converter / PU inner fan t_op
PM330 Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: PDS, p0120
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 [h] 4294967295 [h] 0 [h]
p0287[0...1] Ground fault monitoring thresholds / Gnd flt threshold
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.0 [%] 100.0 [%] [0] 6.0 [%]
[1] 16.0 [%]