Operating Instructions
SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
227
2 Parameters
2.2 List of parameters
Note: To avoid remagnetization processes for load-dependent flux characteristics and for fast load changes, the time
constant to reduce the flux setpoint must be set to an appropriately high value.
As a consequence, it is preset with a multiple of the time constant used for the flux build up.
Description: The following applies for a synchronous reluctance motor:
Sets the time constant for establishing the flux setpoint for a load-dependent optimum flux characteristic.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1578
Note: To quickly establish the flux for torque changes, an appropriately short time constant for the flux build-up must be
selected.
It is preset with the inverse value of the rated motor frequency (p0310).
Description: Sets the efficiency optimization.
When optimizing the efficiency, the flux setpoint of the closed-loop control is adapted as a function of the load.
For p1580 = 100 %, under no-load operating conditions, the flux setpoint is reduced to 50 % of the rated motor flux.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p0500
Note: It only makes sense to activate this function if the dynamic response requirements of the speed controller are low.
In order to avoid oscillations, if required, the speed controller parameters should be adapted (increase Tn, reduce
Kp).
Further, the smoothing time of the flux setpoint filter (p1582) should be increased.
Description: Sets the efficiency optimization.
When optimizing the efficiency, the flux setpoint of the closed-loop control is adapted as a function of the load.
For p1580 = 100 %, under no-load operating conditions, the flux setpoint is reduced to 50 % of the rated motor flux.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Note: It only makes sense to activate this function if the dynamic response requirements of the speed controller are low.
In order to avoid oscillations, if required, the speed controller parameters should be adapted (increase Tn, reduce
Kp).
Further, the smoothing time of the flux setpoint filter (p1582) should be increased.
p1579[0...n] Flux reduction flux build-up time constant / Flux red incr T
Access level: 3 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6791
Min Max Factory setting
0 [ms] 5000 [ms] 4 [ms]
p1580[0...n] Efficiency optimization / Efficiency opt.
PM230 Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6722
Min Max Factory setting
0 [%] 100 [%] 80 [%]
p1580[0...n] Efficiency optimization / Efficiency opt.
PM240
PM250, PM260
Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6722
Min Max Factory setting
0 [%] 100 [%] 0 [%]