Operating Instructions
Application examples
Factory settings
7
82 | 118
Siemens A5E36496664A_f
Smart Infrastructure 2021-10-11
7 Application examples
Basic commissioning (Carrying out basic commissioning [➙ 55]) is a prerequisite
for the implementation of the application examples. During basic commissioning,
the applications below can be parameterized directly via the macro parameter
p0015. If the applications have to be set subsequently, the device must be set to
commissioning state.
Example: p0010 = 1 → p0015 = 101 → p0010 = 0
7.1 Factory settings
Figure 26: Terminal assignment in the factory settings (corresponds to MacPar15 = 12)
7.2 Universal application
● Macro 101 "Universal application"
● Setpoint via a 0...10 V signal
● Analog setpoint can be overridden with 3 fixed speeds
● Flying restart and automatic restart activated
● Essential service mode (in the event of fire) with a
fixed setpoint
● Error message: Digital output 0
● Status display: Digital output 2
Notice:
In the case of the extended emergency mode, the customer
can no longer lodge any claims for warranty. Extended
emergency mode and the faults which arise during this
mode are logged in a password-protected memory and can
be read by the repair center.
Setpoint 0 - 10 V
Control
System
9
5
6
7
3
4
AI0+
AI0-
DI0
DI1
DI2
P24V
25
24
23
22
21
20
19
18
Fault
DO0
DO1
DO2
ON / OFF
Reverse
Acknowledge
Alarm
Operation
28
69
GND
DI COM
AO0+
AO0-
AO1+
AO1-
12
13
26
27
Speed
(0..20mA)
Output current
(0..20mA)