Operating Instructions

Parameters
List of parameters
1-44
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Displays the flux setpoint.
Description: Displays the flux actual value.
Index: [0] = Unsmoothed
[1] = Smoothed
Description: Displays the actual active power factor.
This value refers to the electrical power of the basic fundamental signals at the output terminals of the converter.
Description: Displays the actual phase voltage.
Index: [0] = Phase U
[1] = Phase V
[2] = Phase W
Note: The values are determined from the transistor power-on duration.
Description: Defines whether the motor and drive converter power settings (e.g. rated motor power, p0307) are expressed in
[kW] or [hp].
Depending on the selection, the rated motor frequency (p0310) is either set to 50 Hz or 60 Hz.
For p0100 = 0, 2, the following applies: The power factor (p0308) should be parameterized.
For p0100 = 1, the following applies: The efficiency (p0309) should be parameterized.
r0083 CO: Flux setpoint / Flex setp
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 5722
Min Max Factory setting
- [%] - [%] - [%]
r0084[0...1] CO: Flux actual value / Flux act val
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 6730, 6731
Min Max Factory setting
- [%] - [%] - [%]
r0087 CO: Actual power factor / Cos phi act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
r0089[0...2] Actual phase voltage / U_phase act val
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Units group: 5_3 Unit selection: p0505 Func. diagram: 6719
Min Max Factory setting
- [V] - [V] - [V]
p0100 IEC/NEMA mot stds / IEC/NEMA mot stds
Access level: 1 Calculated: - Data type: Integer16
Can be changed: C(1) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 2 0