Operating Instructions

SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
47
2 Parameters
2.2 List of parameters
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: r0031, p0045
Note: The value is available smoothed (r0031 with 100 ms, r0080[1] with p0045) and unsmoothed (r0080[0]).
Description: Displays the instantaneous active power.
Index: [0] = Unsmoothed
[1] = Smoothed with p0045
[2] = Electric power
Dependency: Refer to: r0032
Note: The mechanical active power is available smoothed (r0032 with 100 ms, r0082[1] with p0045) and unsmoothed
(r0082[0]).
Description: Displays the flux setpoint.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Description: Displays the flux actual value.
Index: [0] = Unsmoothed
[1] = Smoothed
Description: Displays the actual active power factor.
This value refers to the electrical power of the basic fundamental signals at the output terminals of the converter.
r0082[0...2] CO: Active power actual value / P_act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: r2004 Dyn. index: -
Unit group: 14_5 Unit selection: p0505 Func. diagram: 6714, 6799
Min Max Factory setting
- [kW] - [kW] - [kW]
r0083 CO: Flux setpoint / Flex setp
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 5722
Min Max Factory setting
- [%] - [%] - [%]
r0084[0...1] CO: Flux actual value / Actual flux
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 6730, 6731
Min Max Factory setting
- [%] - [%] - [%]
r0087 CO: Actual power factor / Cos phi act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -