Operating Instructions

2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
404 List Manual, 04/2018, A5E33838102
Dependency: A valid COB-ID can only be set for the available (existing) channel.
Note: Corresponds to the CANopen object 1401 hex.
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
Description: Sets the communication parameters for CANopen Receive Process Data Object 3 (RPDO 3).
Index: [0] = PDO COB-ID
[1] = PDO transmission type
Dependency: A valid COB-ID can only be set for the available (existing) channel.
Note: Corresponds to the CANopen object 1402 hex.
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
Description: Sets the communication parameters for CANopen Receive Process Data Object 4 (RPDO 4).
Index: [0] = PDO COB-ID
[1] = PDO transmission type
Dependency: A valid COB-ID can only be set for the available (existing) channel.
Note: Corresponds to the CANopen object 1403 hex.
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
Description: Sets the communication parameters for CANopen Receive Process Data Object 5 (RPDO 5).
Index: [0] = PDO COB-ID
[1] = PDO transmission type
Dependency: A valid COB-ID can only be set for the available (existing) channel.
Note: Corresponds to the CANopen object 1404 hex.
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
p8702[0...1] CAN Receive PDO 3 / Receive PDO 3
CU230P-2_CAN Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(3), T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 9204, 9206
Min Max Factory setting
0000 hex 8000 06DF hex [0] 8000 06DF hex
[1] 00FE hex
p8703[0...1] CAN Receive PDO 4 / Receive PDO 4
CU230P-2_CAN Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(3), T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 9204, 9206
Min Max Factory setting
0000 hex 8000 06DF hex [0] 8000 06DF hex
[1] 00FE hex
p8704[0...1] CAN Receive PDO 5 / Receive PDO 5
CU230P-2_CAN Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(3), T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 9204
Min Max Factory setting
0000 hex 8000 06DF hex [0] 8000 06DF hex
[1] 00FE hex