Operating Instructions
SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
369
2 Parameters
2.2 List of parameters
Description: Displays the commissioning steps that have been carried out.
Note: The individual bits are only set if the appropriate action has been initiated and successfully completed.
The identification final display is reset when changing the type plate parameters.
Description: Displays the base voltage for the alternating voltage in the context of motor data identification.
0:
No alternating voltages. The function is deactivated.
<0:
Automatic determination of the base voltage and wobbulation / self-setting based on the converter and the connected
motor.
Otherwise:
Base voltage for alternating current generation in volts (wobbulation active).
r3925[0...n] Identification final display / Ident final_disp
Access level: 3 Calculated: p0340 = 1 Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Motor/control parameters calculated (p0340
= 1, p3900 > 0)
Yes No -
02 Motor data identification carried out at
standstill (p1910 = 1)
Yes No -
03 Rotating measurement carried out (p1960 =
1, 2)
Yes No -
08 Identified motor data are automatically
backed up
Yes No -
11 Automatic parameterization as Standard
Drive Control
Yes No -
12 Automatic parameterization as Dynamic
Drive Control
Yes No -
14 First motor commissioning Yes No -
15 Equivalent circuit diagram parameters
changed
Yes No -
18 Circle identification executed Yes No -
r3926[0...n] Voltage generation alternating base voltage amplitude / U_gen altern base
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: MDS
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [V] - [V] - [V]