Operating Instructions

Technical data
Functional data
9
112 | 118
Siemens A5E36496664A_f
Smart Infrastructure 2021-10-11
Permissible cable lengths IP55
Cable length Inverter, motor cable EMC acc. IEC/EN61800-3
*)
25 m
Inverters with Category C2 filters
Shielded motor cable
First Environment, Category C2
Inverters with Category C1 filters
Shielded motor cable
First Environment, Category C1 (in relation
to the harmonic currents)
*)
50 m
Inverters with Category C2 filters
Shielded motor cable
Second Environment, Category C3
Inverters with Category C1 filters
Shielded motor cable
Second Environment, Category C2
Valid for FSA … FSC
100 m
Inverters with Category C2 filters
Unshielded motor cable
No EMC category
Inverters with Category C1 filters
UNshielded motor cable
No EMC category
*) Category C2 corresponds to class A according to EN 55011. Category C1 corresponds to class B
according to EN 55011 for conducted interference emission.
**) Ferrite cores required, see chapter "Establishing a line and motor connection" in the installation
manual "SINAMICS G120P PM230 Power Module, IP55”,
A5E35319202B, SIOS Entry-ID: 109744235.
Permissible cable lengths IP20
Length Inverter, motor cable EMC acc. IEC/EN61800-3
*)
25 m
Inverter with integrated filter (cate-
gory C2),
Shielded motor cable
Second environment, category C2
50 m
Inverter with integrated filter (cate-
gory C2),
Shielded motor cable
Second environment, category C3
Inverter without filter
External category C1 filter
Shielded motor cable
First environment, category C1
Inverter with or without filter
Shielded motor cable
No EMC category
100 m
Inverter with or without filter
Unshielded motor cable
No EMC category
150 m
Inverter without filter
External category C1 filter
Shielded motor cable
Output reactor
Second environment, category C2