Operating Instructions

Parameters
List of parameters
1-302
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Sets the operating mode for the energy-saving mode function.
Value: 0: Energy-saving mode inhibited
1: Energy-saving mode activated
Dependency: Refer to: p2200, p2251
Refer to: A07325
Caution: When this function is active, the motor can start again automatically.
Note: When the energy-saving mode function (p2398 = 1) is activated, its behavior is defined as to whether the technol-
ogy controller is additionally switched in (closed-loop) or switched out (open-loop).
The technology controller is enabled via binector input p2200 and its mode is set in p2251.
p2200 = 0, p2251 = 0:
Energy-saving mode operates without technology controller (open-loop)
p2200 = 1, p2251 = 0:
Energy-saving mode operates with technology controller (closed-loop)
Description: Displays the status word for the energy-saving mode function.
Dependency: Refer to: p2398
Refer to: A07325
Description: Sets a fixed percentage.
Dependency: Refer to: p2901, p2930
p2398 Energy-saving mode / En_save mode
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0
r2399.0...8 CO/BO: Energy-saving mode status would / En_save ZSW
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Energy-saving mode enabled (p2398 <> 0) Yes No -
01 Energy-saving mode active Yes No -
02 Energy-saving mode delay time active Yes No -
03 Energy-saving mode boost active Yes No -
04 Energy-saving mode motor switched off Yes No -
05 Energy-saving mode switched off cyclic
restart active
Yes No -
06 Energy-saving mode motor restarts Yes No -
07 Energy-saving mode supplies total setpoint
for ramp-fct. gen.
Yes No -
08 Energy-saving mode bypasses ramp-fct.
gen. in setpoint channel
Yes No -
p2900[0...n] CO: Fixed value 1 [%] / Fixed value 1 [%]
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 1021
Min Max Factory setting
-10000.00 [%] 10000.00 [%] 0.00 [%]