Operating Instructions

Installing
EMC-compliant installation (examples)
5
50 | 118
Siemens A5E36496664A_f
Smart Infrastructure 2021-10-11
Using two examples, the following diagram shows the EMC-compliant installation
of the Power Module with and without shield plate.
You must use the shield plate to achieve EMC-compliant installation of devices in
frame sizes FSA to FSC.
The shield of the control cable must be attached to both the shield plate of the
Control Unit and the shield plate of the Power Module.
Figure 22: EMC-compliant wiring IP20
Item Designation
1
Line connection cable (unshielded) for Power Modules with integrated line filter.
If you use an external line filter, you will need a shielded cable between the line filter and
the Power Module.
2
Motor connection
3
Line supply cable (unshielded)
4
Motor connection cable (shielded)
5
Cable shield
6
Cable clamps for establishing the connection between the shield and the mounting plate
over a large surface area
7
Serrated collar
8
Cable tie
9
Metal mounting plate (unpainted and with a good electrical conductivity)
10
Shield plate (option)