10 Appendix Commissioning report
Parameter Function Factory setting Setting
P0970 Restoring the factory setting -
P1300 Control type 2 (U/f parabolic)
P0100 Motor standard 0 (IEC motor)
P0304 Rated motor voltage [V]
P0305 Rated motor current [A]
P0307 Motor power [kW]
P0311 Rated motor speed [rpm]
P1900 Motor data identification selection 0
P0015 Macro parameter 12
P1080 Minimum speed [rpm] 0
P1120 Ramp-up time [s] 10
P1121 Ramp-down time [s] 30
P0601 Motor temperature sensor 0 (no sensor)
P0731 (0) Digital output function 0 52.3 (Fault)
P0732 (0) Digital output function 1 52.7 (Alarm)
P0732 (0) Digital output function 2 52.3 (Operation)
P0757 (0) x1 value for ADC scaling [V / mA] 0
P0758 (0) y1 value for ADC scaling [%] 0
P1082 Maximum speed [rpm] 1500
P1200 Flying restart operating mode 0 (flying restart inactive)
P1210 Automatic Restart 0 (disabled)
P1211 No. of start attempts 3
P1212 Time until the first restart [s] 1
P1213[0] Monitoring time for restart [s] 60
P1213[1] Time to reset the start counter [s] 0
P1240 Configuration of the Vdc controller 1
P1820 Reverse output phase sequence 0
P2000 Reference speed [rpm] 1500