Operating Instructions

4.4.6 Connecting the inverter with the PM240P-2 Power Module
/LQHILOWHU 2XWSXWUHDFWRU,QYHUWHU
8
9
:
3( 3(
:
9
8
/
/
/
3( 3(
/
/
/
/
/
/
3(
:
9
8
3(
/
/
/
Figure 4-17 PM240P-2 Power Module connection overview
Table 4-28 Connection, cross-section and tightening torque for PM240P-2 Power Modules
Inverter Connection Cross-section, tightening torque Stripped
insulation
length
Metric Imperial
FSD Line supply,
motor
Screw-type termi‐
nal
10 … 35 mm
2
, 2.5 … 4.5 Nm 20 … 10 AWG, 22 lbf in
8 … 2 AWG, 40 lbf in
18 mm
FSE 25 … 70 mm
2
, 8 … 10 Nm 6 … 3/0 AWG, 88.5 lbf in 25 mm
FSF Line supply,
motor
Cable lug accord‐
ing to SN71322
35 … 2 × 120 mm
2
,
22 … 25 Nm
1 … 2 × 4/0 AWG, 210 lbf in --
Connections, frame sizes FSD … FSF
You must remove the covers from the connections in order to connect the line supply and
motor cables to the inverter.
)6')6( )6)
Figure 4-18 Remove the connection covers
In addition, for frame sizes FSD and FSE, release the two terminal screws on the connections
for the motor and remove the dummy plug.
Installing
4.4 Connecting the line supply and motor
Converter with the CU230P-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257946B AF 101