Operating Instructions
Parameters
List of parameters
1-196
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Sets a dynamic voltage reserve.
Dependency: Refer to: p0500
Note: In the field weakening range, it must be expected that the control dynamic performance is somewhat restricted due
to the limited possibilities of controlling/adjusting the voltage. This can be improved by increasing the voltage
reserve. Increasing the reserve reduces the steady-state maximum output voltage (r0071).
Description: Sets the efficiency optimization.
When optimizing the efficiency, the flux setpoint of the closed-loop control is adapted as a function of the load.
For p1580 = 100 %, under no-load operating conditions, the flux setpoint is reduced to 50 % of the rated motor flux.
Dependency: Refer to: p0500
Note: It only makes sense to activate this function if the dynamic response requirements of the speed controller are low.
In order to avoid oscillations, if required, the speed controller parameters should be adapted (increase Tn, reduce
Kp).
Further, the smoothing time of the flux setpoint filter (p1582) should be increased.
Description: Sets the efficiency optimization.
When optimizing the efficiency, the flux setpoint of the closed-loop control is adapted as a function of the load.
For p1580 = 100 %, under no-load operating conditions, the flux setpoint is reduced to 50 % of the rated motor flux.
Note: It only makes sense to activate this function if the dynamic response requirements of the speed controller are low.
In order to avoid oscillations, if required, the speed controller parameters should be adapted (increase Tn, reduce
Kp).
Further, the smoothing time of the flux setpoint filter (p1582) should be increased.
Description: Sets the efficiency optimization.
When optimizing the efficiency, the flux setpoint of the closed-loop control is adapted as a function of the load.
For p1580 = 100 %, under no-load operating conditions, the flux setpoint is reduced to 50 % of the rated motor flux.
Dependency: Refer to: p0500
p1574[0...n] Voltage reserve dynamic / U_reserve dyn
PM240
PM250, PM260
Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: 5_1 Unit selection: p0505 Func. diagram: 6723, 6724
Min Max Factory setting
0.0 [Vrms] 150.0 [Vrms] 10.0 [Vrms]
p1580[0...n] Efficiency optimization / Efficiency opt.
PM230 Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6722
Min Max Factory setting
0 [%] 100 [%] 80 [%]
p1580[0...n] Efficiency optimization / Efficiency opt.
PM240
PM250, PM260
Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6722
Min Max Factory setting
0 [%] 100 [%] 0 [%]
p1580[0...n] Efficiency optimization / Efficiency opt.
PM330 Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6722
Min Max Factory setting
0 [%] 100 [%] 100 [%]