SINAMICS G120 CU230P-2 Control Units
390 List Manual (LH9), 04/2014, A5E33838102B AA
Description: Sets the signal source for the actual value of the free technology controller 1.
Description: Sets the smoothing time constant (PT1) for the actual value of the free technology controller 1.
Description: Sets the upper limit for the actual value signal of the free technology controller 1.
Dependency: Refer to: p11164
Description: Sets the lower limit for the actual value signal of the free technology controller 1.
Dependency: Refer to: p11164
Description: Sets the inversion of the actual value signal of the free technology controller 1.
Value: 0: No inversion
1: Inversion
Description: Display and connector output for the actual value after the limiter of the free technology controller 1.
p11164 CI: Free tec_ctrl 1 actual value signal source / Ftec1 act v s_s
Access level: 2 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
- - 0
p11165 Free tec_ctrl 1 actual value smoothing time constant / Ftec1 act v T
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0.00 [s] 60.00 [s] 0.00 [s]
p11167 Free tec_ctrl 1 actual value upper limit / Ftec1 act v up lim
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Units group: 9_3 Unit selection: p11126 Func. diagram: 7030
Min Max Factory setting
-200.00 [%] 200.00 [%] 100.00 [%]
p11168 Free tec_ctrl 1 actual value lower limit / Ftec1 act v lo lim
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Units group: 9_3 Unit selection: p11126 Func. diagram: 7030
Min Max Factory setting
-200.00 [%] 200.00 [%] -100.00 [%]
p11171 Free tec_ctrl 1 actual value inversion / Ftec1 act v inv
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7030
Min Max Factory setting
0 1 0
r11172 CO: Free tec_ctrl 1 actual value after limiter / Ftec1 act v af lim
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Units group: 9_3 Unit selection: p11126 Func. diagram: 7030
Min Max Factory setting
- [%] - [%] - [%]