Operating Instructions
SINAMICS G120 CU230P-2 Control Units
List Manual (LH9), 04/2014, A5E33838102B AA
305
2 Parameters
2.2 List of parameters
Description: Sets the boost speed for the energy-saving mode function.
The motor is accelerated to the energy-saving mode boost speed p2395 for the energy-saving mode boost time
period p2394 before it is brought to a standstill via the down ramp of the setpoint channel (p1121) and subsequently
powered down (pulse inhibit).
Dependency: Refer to: p2394
Caution: The controller is not operational while the boost speed is being impressed. As a result, for example, for pump
applications, it must be ensured that the tank does not overflow as a result of the additional boost. For compressors,
it must be ensured that the boost speed does not result in an overpressure condition.
Description: Sets the maximum shutdown time for the energy-saving mode function.
If the drive is in the energy-saving mode (pulse inhibit) then it is powered up again at the latest after the maximum
power-down time has expired. If the restart conditions are fulfilled earlier, then the drive is correspondingly powered
up earlier.
Danger: The drive automatically powers itself up at the latest after the maximum power-down time has expired.
Caution: Once the maximum shutdown time has expired, the drive switches itself on automatically and accelerates to the start
speed. The technology controller only becomes effective again when this speed is reached (for p2398 = 1).
Depending on the application, e.g. for pumps, it should be ensured that as a result of cyclic starts the tank does not
overflow or for compressors, an overpressure condition does not occur.
Note: Automatic restart once the maximum OFF time has elapsed is de-activated by setting p2396 = 0 s.
Description: Displays the actual output speed for the energy-saving mode function.
Note: Zero is displayed if the boost or starting speed is not active.
Description: Sets the operating mode for the energy-saving mode function.
Value: 0: Energy-saving mode inhibited
1: Energy-saving mode activated
Dependency: Refer to: p2200, p2251
p2395[0...n] Energy-saving mode boost speed / En_sav n_boost
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: p2000 Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: -
Min Max Factory setting
0.000 [rpm] 21000.000 [rpm] 0.000 [rpm]
p2396[0...n] Energy-saving mode max shutdown time / En_sav t_off max
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 [s] 863999 [s] 0 [s]
r2397[0...1] CO: Energy-saving mode output speed actual / En_sav n_outp act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 3_1 Unit selection: p0505 Func. diagram: -
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p2398 Energy-saving mode / En_save mode
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0