8.3.3.1 Tests without a power supply
DANGER
Danger due to electric current!
If the terminals are not accessible externally, do not open the device because you
will be exposed to a great risk and this will invalidate the warranty.
In this case, contact your local Siemens branch office.
Preliminary tests
Check/Test Description OK
Disconnect the
power supply
Ensure that the drive is disconnected from the line supply.
Safeguard Take measures (a mechanical maintenance switch, for example) to
prevent the variable speed drive and the connected motor
(depending on application) from restarting.
Ensure that there is
no voltage present
at the drive.
1. Measure the voltage between L1/L2 and L3.
2. Make sure that the system is completely de-energized.
Damage caused by
external factors
Check whether parts are damaged, for example by corrosion, paint,
moisture, oil, dust, powder, etc.
Electrical damage Look for evidence of flashovers or burning at the power terminals.
These are caused by connecting the power cables incorrectly.
Fuses
1. Check the sizes of the fuses.
2. Make sure that they are not "open".