Operating Instructions
2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
392 List Manual, 04/2018, A5E33838102
Dependency: Refer to: p8409, p8420, p8421, p8422
Notice: This parameter can only be changed when p8409 = 0.
Note: DTC: Digital Time Clock (timer)
RTC: Real-time clock
Description: Sets the weekday on which timer 3 is activated (DTC3).
The switch-on/off time is set in p8431/p8432 and the result displayed via binector output r8433.
Value: 0: Weekday deactivated
1: Weekday activated
Index: [0] = Monday
[1] = Tuesday
[2] = Wednesday
[3] = Thursday
[4] = Friday
[5] = Saturday
[6] = Sunday
Dependency: Refer to: p8409, p8431, p8432, r8433
Notice: This parameter can only be changed when p8409 = 0.
Note: DTC: Digital Time Clock (timer)
RTC: Real-time clock
Description: Sets the switch on time in hours and minutes for timer 3 (DTC3).
BO: r8433 = 1 signal:
The condition for the set weekday (p8430) and switch-on time has been fulfilled.
Index: [0] = Hour (0 ... 23)
[1] = Minute (0 ... 59)
Dependency: Refer to: p8409, p8430, r8433
Notice: This parameter can only be changed when p8409 = 0.
Note: DTC: Digital Time Clock (timer)
RTC: Real-time clock
Description: Sets the switch off time in hours and minutes for timer 3 (DTC3).
BO: r8433 = 0 signal:
The condition for the set weekday (p8430) and switch-off time has been fulfilled.
Index: [0] = Hour (0 ... 23)
[1] = Minute (0 ... 59)
Dependency: Refer to: p8409, p8430, r8433
p8430[0...6] RTC DTC3 weekday of activation / RTC DTC3 day act
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0
p8431[0...1] RTC DTC3 switch-on time / RTC DTC3 t_ON
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 59 0
p8432[0...1] RTC DTC3 off time / RTC DTC3 t_OFF
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 59 0