Operating Instructions

2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
378 List Manual, 04/2018, A5E33838102
Dependency: Refer to: r0034, p0605, p0612, r0632, p5391
Refer to: F07011, A07012, A07014
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: The hysteresis is 2 K.
Description: Sets the fault threshold for monitoring the motor temperature for motor temperature models 1 and 3.
Fault F07011 is output after the fault threshold is exceeded.
The stator winding temperature (r0632) is used to initiate the signal.
The following applies for temperature model 1 (I2t):
- only effective from firmware version 4.7 SP6 and p0612.8 = 1.
- when commissioning a catalog motor for the first time, the threshold value is copied from p0615 to p5391.
Dependency: Refer to: r0034, p0612, p0615, r0632, p5390
Refer to: F07011, A07014
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: The hysteresis is 2 K.
Description: Displays the PROFIenergy mode ID of the effective energy-saving mode.
Value: 0: POWER OFF
2: Energy-saving mode 2
240: Operation
255: Ready
Note: Pe: PROFIenergy profiles
Description: Sets the minimum possible pause time for the energy-saving mode.
The value is the sum of the following times:
- Energy-saving mode transition time
- Operating state transition time regular
- Energy-saving mode, time of minimum stay
Index: [0] = Reserved
[1] = Mode 2
Note: It is not permissible that the value is less than the sum of the "energy-saving mode transition time" and the "operating
state transition time" (system properties).
Pe: PROFIenergy profiles
p5391[0...n] Mot_temp_mod 1/3 fault threshold / F thresh
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Unit group: 21_1 Unit selection: p0505 Func. diagram: 8017
Min Max Factory setting
0.0 [°C] 200.0 [°C] 120.0 [°C]
r5600 Pe energy-saving mode ID / Pe mode ID
CU230P-2_PN Access level: 3 Calculated: - Data type: Integer16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2381, 2382
Min Max Factory setting
0 255 -
p5602[0...1] Pe energy-saving mode pause time minimal / Pe mod t_pause min
CU230P-2_PN Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2381
Min Max Factory setting
300000 [ms] 4294967295 [ms] [0] 300000 [ms]
[1] 480000 [ms]