SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Sets and displays the date on the real-time clock in year, month, and day.
The date is stored in the internal clock block in the drive and continues to run even if the supply voltage for the Con-
trol Unit is interrupted (for approx. 5 days).
Index: [0] = Day (1 ... 31)
[1] = Month (1 ... 12)
[2] = Year (YYYY)
Note: The time from p8400 and p8401 is used to display the fault and alarm times.
The parameter is not reset when the factory setting is restored (p0010 = 30, p0970).
RTC: Real-time clock
Description: Displays the weekday on the real-time clock.
Value: 1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
Note: RTC: Real-time clock
Description: Sets whether the real-time clock outputs an alarm if the time is not synchronized (e.g. if the power supply was
switched off for an extended period).
Value: 0: Alarm A01098 de-activated
1: Alarm A01098 activated
Dependency: Refer to: A01098
Note: RTC: Real-time clock
p8401[0...2] RTC date / RTC date
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 9999 [0] 1
[1] 1
[2] 1970
r8404 RTC weekday / RTC weekday
Access level: 3 Calculated: - Data type: Integer16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
1 7 -
p8405 Activate/de-activate RTC alarm A01098 / RTC A01098 act
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 1