Data Sheet for Product

14
Siemens
N5111
2021-12-14
Derating factors
Derating table
The rated power based on the rated output current /N. The rated output current/N is based
on the duty cycle for low overload (low overload LO).
Rated output
at 3 AC 50 Hz 400 V
Rated output current in A
for a pulse frequency of
Kw
HP
4 kHz
6 kHz
8 kHz
10 kHz
12 kHz
14 kHz
16 kHz
0.75
1.0
2.2
1.87
1.54
1.32
1.10
0.99
0.88
1.1
1.5
3.1
2.64
2.17
1.86
1.55
1.40
1.24
1.5
2.0
4.1
3.49
2.87
2.46
2.05
1.85
1.64
2.2
3.0
5.9
5.02
4.13
3.54
2.95
2.66
2.36
3.0
4.0
7.7
6.55
5.39
4.62
3.85
3.47
3.08
4.0
5.0
10.2
8.67
7.14
6.12
5.1
4.59
4.08
5.5
7.5
13.2
11.22
9.24
7.92
6.6
5.94
5.28
7.5
10
18.0
15.3
12.6
10.8
9.0
8.1
7.2
11.0
15
26.0
22.1
18.2
15.6
13.0
11.7
10.4
15.0
20
32.0
27.2
22.4
19.2
16.0
14.4
12.8
18.5
25
38.0
32.3
26.6
22.8
19.0
17.1
15.2
22
30
45.0
38.25
31.5
27.0
22.5
20.25
18.0
30
40
60.0
52.7
43.4
37.2
31.0
27.9
24.8
37
50
75.0
63.75
52.5
45.0
37.5
33.75
30.0
45
60
90.0
76.5
63.0
54.0
45.0
40.5
36.0
55
75
110
93.5
77.0
75
100
145
123.3
101.5
90
125
178
151.3
124.6
Derating in relation to the ambient temperature
Low overload (LO) for Power
Modules PM230, frame sizes
A to F
100
25
35
0
50
%
75
85
60°C504010 3020
0
G
_
D
0
1
1
_
D
E
_
0
0
3
0
9
C
(
%
)
T (°C)
T (°C) = ambient temperature
C (%) = permissible output current