Operating Instructions
2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
360 List Manual, 04/2018, A5E33838102
Description: Sets the signal source for command 1 for the two-wire control/three-wire control.
Dependency: Refer to: p0015, p3331, p3332, r3333, p3334
Note: The mode of operation of this binector input is dependent on the wire control set in p0015.
Description: Sets the signal source for command 2 for the two-wire control/three-wire control.
Dependency: Refer to: p0015, p3330, p3332, r3333, p3334
Note: The mode of operation of this binector input is dependent on the wire control set in p0015.
Description: Sets the signal source for command 3 for the two-wire control/three-wire control.
Dependency: Refer to: p0015, p3330, p3331, r3333, p3334
Note: The mode of operation of this binector input is dependent on the wire control set in p0015.
Description: Displays the control word for the two wire control/three wire control.
The control signals are dependent on the wire control set in p0015 and the signal states at the digital inputs.
Dependency: Refer to: p0015, p3330, p3331, p3332, p3334
p3330[0...n] BI: 2/3 wire control command 1 / 2/3 wire cmd 1
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 2272, 2273
Min Max Factory setting
- - 0
p3331[0...n] BI: 2/3 wire control command 2 / 2/3 wire cmd 2
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 2272, 2273
Min Max Factory setting
- - 0
p3332[0...n] BI: 2/3 wire control command 3 / 2/3 wire cmd 3
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 2273
Min Max Factory setting
- - 0
r3333.0...3 CO/BO: 2/3 wire control control word / 2/3 wire STW
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2272, 2273
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON Yes No -
01 Reversing Yes No -
02 ON inverted Yes No -
03 Reversing inverted Yes No -