Operating Instructions
SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
355
2 Parameters
2.2 List of parameters
Description: Displays the fault value of the oldest active fault.
Dependency: Refer to: r2131, r3132
Description: Displays the component number of the oldest fault that is still active.
Dependency: Refer to: r2131, r3131
Description: Sets the signal source for the speed actual value of the load monitoring.
Dependency: Refer to: r2169, p2181, p2192, p2193, p3231
Refer to: A07920, A07921, A07922, F07923, F07924, F07925
Note: The parameter is only effective for p2193 = 2.
Description: Sets the permissible speed deviation during load monitoring (for p2193 = 2).
Dependency: Refer to: r2169, p2181, p2193, p3230
Refer to: A07920, A07921, A07922, F07923, F07924, F07925
Description: Sets the signal source for detecting a failure.
Dependency: Refer to: p2192, p2193
Refer to: F07936
Note: Monitoring is triggered with a 0 signal, as soon as the time in p2192 has expired.
r3131 CO: Actual fault value / Act fault val
Access level: 3 Calculated: - Data type: Integer32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 8060
Min Max Factory setting
- - -
r3132 CO: Actual component number / Comp_no act
Access level: 3 Calculated: - Data type: Integer32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 8060
Min Max Factory setting
- - -
p3230[0...n] CI: Load monitoring speed actual value / Load monit n_act
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2000 Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 8012, 8013
Min Max Factory setting
- - 0
p3231[0...n] Load monitoring speed deviation / Load monit n_dev
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Func. diagram: 8013
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 150.00 [rpm]
p3232[0...n] BI: Load monitoring failure detection / Load_moni fail_det
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 8013
Min Max Factory setting
- - 1