Operating Instructions
2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
348 List Manual, 04/2018, A5E33838102
Caution: When the "hibernation mode" function is active, the motor can start again automatically.
Note: When the "hibernation mode" function (p2398 = 1) is activated, its behavior is defined as to whether the technology
controller is additionally switched in (closed-loop) or switched out (open-loop).
The technology controller is enabled via binector input p2200 and its mode is set in p2251.
p2200 = 0, p2251 = 0:
Hibernation mode operates without technology controller (open-loop)
p2200 = 1, p2251 = 0:
Hibernation mode operates with technology controller (closed-loop)
Description: Display and BICO output for the status word of the "hibernation mode" function.
Dependency: Refer to: p2398
Refer to: A07325
Description: Setting and connector output for a fixed percentage value.
Dependency: Refer to: p2901, r2902, p2930
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note: The value can be used to interconnect a scaling function (e.g. scaling the main setpoint).
Description: Setting and connector output for a fixed percentage value.
Dependency: Refer to: p2900, p2930
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note: The value can be used to interconnect a scaling function (e.g. scaling of the supplementary setpoint)
r2399.0...8 CO/BO: Hibernation mode status words / Hib ZSW
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7038
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Hibernation mode enabled (p2398 <> 0) Yes No -
01 Hibernation mode active Yes No -
02 Hibernation mode delay active Yes No -
03 Hibernation boost active Yes No -
04 Hibernation mode motor switched off Yes No -
05 Hibernation mode switched off cyclic restart
active
Yes No -
06 Hibernation motor motor restarts Yes No -
07 Hibernation mode supplies total setpoint for
ramp-fct generator
Yes No -
08 Hibernation mode bypasses ramp-fct
generator in setpoint channel
Yes No -
p2900[0...n] CO: Fixed value 1 [%] / Fixed value 1 [%]
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 1021
Min Max Factory setting
-10000.00 [%] 10000.00 [%] 0.00 [%]
p2901[0...n] CO: Fixed value 2 [%] / Fixed value 2 [%]
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 1021
Min Max Factory setting
-10000.00 [%] 10000.00 [%] 0.00 [%]