Operating Instructions
2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
336 List Manual, 04/2018, A5E33838102
Caution: The upper starting point must be set higher than the lower starting point (p2314 > p2313).
Note: Kp adaptation is activated with p2252.7 = 1.
Description: Sets the upper activation point for the adaptation of proportional gain Kp for the technology controller.
Dependency: Refer to: p2310, p2311, p2312, p2313, p2315, r2316
Caution: The upper starting point must be set higher than the lower starting point (p2314 > p2313).
Note: Kp adaptation is activated with p2252.7 = 1.
Description: Sets the signal source to scale the results of the adaptation of the proportional gain Kp for the technology controller.
Dependency: Refer to: p2310, p2311, p2312, p2313, p2314, r2316
Note: Kp adaptation is activated with p2252.7 = 1.
Description: Display and connector output for the output signal of the adaption of proportional gain Kp for the technology
controller.
Dependency: Refer to: p2252, p2310, p2311, p2312, p2313, p2314, p2315
Description: Sets the signal source for the input value of the adaptation of integral time Tn for the technology controller.
Dependency: Refer to: p2252, p2318, p2319, p2320, p2321, r2322
Note: Tn adaptation is activated with p2252.8 = 1.
p2314 Technology controller Kp adaptation upper starting point / Kp adapt upper pt
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7959
Min Max Factory setting
0.00 [%] 400.00 [%] 100.00 [%]
p2315 CI: Technology controller Kp adaptation scaling signal source / Kp adapt scal s_s
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7959
Min Max Factory setting
- - 1
r2316 CO: Technology controller, Kp adaptation output / Kp adapt outp
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7959
Min Max Factory setting
- - -
p2317 CI: Technology controller Tn adaptation input value signal source / Tn adapt inp s_src
Access level: 2 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7959
Min Max Factory setting
- - 0