Description: Sets the optimum load angle for synchronous motors with reluctance torque.
The load angle is measured at the rated motor current.
Caution: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note: This parameter has no significance for induction motors.
For synchronous motors without reluctance torque, a angle of 90 degrees must be set.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (refer to p0300).
Description: Sets the reluctance torque constant for synchronous motors with reluctance torque (e.g. 1FE ... motors).
This parameter has no significance for induction motors.
Caution: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note: For synchronous motors without reluctance torque, the value 0 must be set.
Description: Sets the current for the pole position identification routine.
For a two-stage technique, the current is set for the 2nd phase.
Dependency: Refer to: p0325, p1980, r1984, r1985, r1987
Caution: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Description: Displays the rated motor slip.
Dependency: The rated slip is calculated from the rated frequency, rated speed and number of pole pairs.
Refer to: p0310, p0311, r0313
Note: The parameter is not used for synchronous motors (p0300 = 2xx).
p0327[0...n] Optimum motor load angle / Mot phi_load opt
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Data set: MDS
Units group: - Unit selection: -
Min Max Factory setting
0.0 [°] 135.0 [°] 90.0 [°]
p0328[0...n] Motor reluctance torque constant / Mot kT_reluctance
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Data set: MDS
Units group: - Unit selection: -
Min Max Factory setting
-1000.00 [mH] 1000.00 [mH] 0.00 [mH]
p0329[0...n] Motor pole position identification current / Mot PolID current
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Data set: MDS
Units group: - Unit selection: -
Min Max Factory setting
0.00 [Arms] 10000.00 [Arms] 0.00 [Arms]
r0330[0...n] Rated motor slip / Mot slip_rated
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Data set: MDS
Units group: - Unit selection: -
Min Max Factory setting
- [Hz] - [Hz] - [Hz]