Operating Instructions

Communication via RS485
5.4 Communication using Modbus RTU
Fieldbuses
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
133
5.4.4
Mapping tables - inverter data
Table 5- 12 Assigning the Modbus register to the parameters - On and outputs
Regis-
ter
Description
Ac-
cess
Unit
Scaling
ON-/OFF
text/value range
Data / parameter
Digital outputs
40200 DO 0 R/W -- 1 HIGH LOW p0730, r747.0, p748.0
40201
DO 1
R/W
--
1
HIGH
LOW
p0731, r747.1, p748.1
40202 DO 2 R/W -- 1 HIGH LOW p0732, r747.2, p748.2
Analog outputs
40220
AO 0
R
%
100
-100.0 … 100.0
r0774.0
40221
AO 1
R
%
100
-100.0 … 100.0
r0774.1
40523
AO 0
R/W
%
100
-199.99 … 199.99
p0791.0
40524
AO 1
R/W
%
100
-199.99 … 199.99
p0791.1
Digital inputs
40240
DI 0
R
--
1
HIGH
LOW
r0722.0
40241
DI 1
R
--
1
HIGH
LOW
r0722.1
40242
DI 2
R
--
1
HIGH
LOW
r0722.2
40243
DI 3
R
--
1
HIGH
LOW
r0722.3
40244
DI 4
R
--
1
HIGH
LOW
r0722.4
40245
DI 5
R
--
1
HIGH
LOW
r0722.5
Analog inputs
40260
AI 0
R
%
100
-300.0 … 300.0
r0755 [0]
40261
AI 1
R
%
100
-300.0 … 300.0
r0755 [1]
40262
AI 2
R
%
100
-300.0 … 300.0
r0755 [2]
40263 AI 3 R % 100 -300.0 … 300.0 r0755 [3]