Operating Instructions
SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
473
2 Parameters
2.2 List of parameters
Description: Display parameter for quotients Y = X1 / X2, the integer number quotients YIN, and division remainder MOD = (Y -
YIN) x X2 of instance DIV 1 of the divider.
Index: [0] = Quotient Y
[1] = Integer number quotient YIN
[2] = Div remainder MOD
Description: Display parameter for the signal QF that the divisor X2 of instance DIV 1 of the divider is zero.
X2 = 0.0 => QF = 1
Description: Setting parameter for the run-time group in which instance DIV 1 of the divider is to be called.
Value: 5: Run-time group 5
6: Run-time group 6
9999: Do not calculate
Description: Setting parameter for the run sequence of instance DIV 1 within the run-time group set in p20126.
Note: The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
Description: Sets the signal source of the input quantity X of instance AVA 0 of the absolute value generator with sign evaluation.
r20124[0...2] CO: DIV 1 quotient / DIV 1 quotient
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7222
Min Max Factory setting
- - -
r20125 BO: DIV 1 divisor is zero QF / DIV 1 divisor=0 QF
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7222
Min Max Factory setting
- - -
p20126 DIV 1 run-time group / DIV 1 RTG
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7222
Min Max Factory setting
5 9999 9999
p20127 DIV 1 run sequence / DIV 1 RunSeq
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7222
Min Max Factory setting
0 32000 310
p20128 CI: AVA 0 input X / AVA 0 input X
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7224
Min Max Factory setting
- - 0