Operating Instructions

List of parameters
Parameters
1-47
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Displays the unique code number of the power unit.
Note: r0200 = 0: No power unit data found
Description: Sets the actual code number from r0200 to acknowledge the power unit being used.
When commissioned for the first time, the code number is automatically transferred from r0200 into p0201.
Note: The parameter is used to identify when the drive is being commissioned for the first time.
The power unit commissioning can only be exited (p0201 = r0200), if the actual and acknowledged code numbers
are identical (p0010 = 2).
When the code number is changed, the connection voltage (p0210) is checked and, if necessary, adjusted.
Description: Displays the type of power unit found.
Value: 2: MICROMASTER 440
3: MICROMASTER 411
4: MICROMASTER 410
5: MICROMASTER 436
6: MICROMASTER 440 PX
7: MICROMASTER 430
100: SINAMICS S
101: SINAMICS S (value)
102: SINAMICS S (combi)
103: SINAMICS S120M (distributed)
112: PM220 (SINAMICS G120)
113: PM230 (SINAMICS G120)
114: PM240 (SINAMICS G120)
115: PM250 (SINAMICS G120 / S120)
116: PM260 (SINAMICS G120)
118: SINAMICS G120 Px
120: PM340 (SINAMICS S120)
130: PM250D (SINAMICS G120D)
133: SINAMICS G120C
135: SINAMICS PMV40
136: SINAMICS PMV60
137: SINAMICS PMV80
138: SINAMICS G110M
150: SINAMICS G
151: PM330 (SINAMICS G120)
200: SINAMICS GM
r0200[0...n] Power unit code number actual / PU code no. act
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: PDS
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
p0201[0...n] Power unit code number / PU code no
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: C(2) Scaling: - Dyn. index: PDS
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 65535 0
r0203[0...n] Actual power unit type / PU actual type
Access level: 3 Calculated: - Data type: Integer16
Can be changed: - Scaling: - Dyn. index: PDS
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
2 400 -