Operating Instructions

Communication via PROFIBUS and PROFINET
3.6 Communication via PROFINET
Fieldbuses
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
59
3.6
Communication via PROFINET
You can either integrate the inverter in a PROFINET network or communicate with the
inverter via Ethernet.
The inverter in PROFINET IO operation
Figure 3-20 The inverter in PROFINET IO operation
The inverter supports the following functions:
RT
IRT: The inverter forwards the clock synchronism, but does not support clock
synchronism.
MRP: Media redundancy, impulsed with 200 ms. Requirement: Ring topology
MRPD: Media redundancy, bumpless. Requirement: IRT and the ring topology created in
the control
Diagnostic alarms in accordance with the error classes specified in the PROFIdrive
profile.
Device replacement without removable data storage medium
Shared Device for Control Units with fail-safe functions
The inverter as Ethernet node
Figure 3-21 The inverter as Ethernet node