Operating Instructions
Parameters
List of parameters
1-362
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Dependency: Refer to: r2050, r2090, r2091, r2092, r2093, r8750, r8795
Note: The following BICO interconnections are automatically established if the CANopen control word is mapped at one
of the locations x = 0 ... 3 in the receive process data buffer.
BI: p0840.0 = r209x.0
BI: p0844.0 = r209x.1
BI: p0848.0 = r209x.2
BI: p0852.0 = r209x.3
BI: p2103.0 = r209x.7
The write access is rejected if a CANopen control word is not mapped at one of these locations.
This also causes the project download of the commissioning software to be canceled.
Description: Setting for the CANopen control word bit 8 "Stop" (CANopen STW.8).
Value: -1: No interconn
1: Interconnection CANopen STW.8 with p1142
3: Interconnection CANopen STW.8 with p1140
Dependency: Refer to: r2050, r8750, r8795
Note: Corresponds to CANopen object 605D hex.
The BICO interconnection is established, if the CANopen control word is mapped at one of the locations x = 0 ... 3
in the receive process data buffer.
Description: Display and connector output to interconnect standardized I16 setpoint CANopen objects of the velocity mode for
SDO transfer.
An index can only be used, if the corresponding object has not been mapped in a PDO.
Index: [0] = VL Target Velocity
Note: Re index 0:
Corresponds to the CANopen object 6042 hex.
The displayed parameter value is scaled via the reference speed p2000:
4000 hex corresponds to p2000
Description: Access to the CANopen control word using SDO transfer.
p8791 CAN stop option code / Stop opt_code
CU230P-2_CAN Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(3), T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
-1 3 -1
r8792[0] CO: CAN velocity mode I16 setpoint / Vel mod I16 set
CU230P-2_CAN Access level: 3 Calculated: - Data type: Integer16
Can be changed: - Scaling: 4000H Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
r8795.0...15 CO/BO: CAN control word / Control word
CU230P-2_CAN Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON/OFF1 Yes No -
01 Do not activate coast down Yes No -
02 Do not activate a Quick Stop Yes No -
03 Operation enable Yes No -