Operating Instructions

Parameters
List of Parameters
1-222
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Sets the minimum time for falling below the changeover speed when changing from closed-loop controlled opera-
tion to open-loop controlled operation.
Dependency: Refer to: p1755, p1756
Description: Sets the minimum time for exceeding the changeover speed when changing from open-loop controlled operation to
closed-loop controlled operation.
Dependency: Refer to: p1755, p1756
Note: When p1759 = 2000 ms, the delay time becomes ineffective and the model changeover is determined by the output
frequency only.
Description: Induction motor (ASM):
Displays the referred imaginary system deviation for the adaptation circuit of the motor model.
Permanent-magnet synchronous motor (PESM):
Displays the system deviation for speed adaptation.
r1762.0: Angular deviation [rad-el] of the estimated EMF.
r1762.1: Angular deviation [electr. deg.] of the low-level signal response for pulse technique.
Index: [0] = Deviation Model1
[1] = Deviation Model2
Description: Induction motor (ASM):
Displays the referred real system deviation for the adaptation circuit of the motor model.
Permanent-magnet synchronous motor (PESM):
Not used.
p1758[0...n] Motor model changeover delay time closed/open-loop control / MotMod t cl_op
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
100 [ms] 10000 [ms] 500 [ms]
p1759[0...n] Motor model changeover delay time open/closed-loop control / MotMod t op_cl
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0 [ms] 2000 [ms] 0 [ms]
r1762[0...1] Motor model deviation component 1 / MotMod dev comp 1
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
r1763 Motor model deviation component 2 / MotMod dev comp 2
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -