Description: Sets the proportional gain for the DC-link voltage controller (Vdc_min controller, Vdc_max controller).
Dependency: The effective proportional gain is obtained taking into account p1243 (Vdc_max controller dynamic factor) and the
DC link capacitance of the power unit.
Description: Sets the integral time for the DC-link voltage controller (Vdc_min controller, Vdc_max controller).
Dependency: The effective integral time is obtained taking into account p1243 (Vdc_max controller dynamic factor).
Note: p1251 = 0: The integral component is de-activated.
Description: Sets the rate time constant for the DC-link voltage controller (Vdc_min controller, Vdc_max controller).
Dependency: The effective rate time is obtained taking into account p1243 (Vdc_max controller dynamic factor).
Description: Activates/de-activates the automatic sensing of the switch-in level for the Vdc_max controller.
Value: 0: Automatic detection inhibited
1: Automatic detection enabled
Description: Activates/de-activates the automatic sensing of the switch-in level for the Vdc_max controller.
Value: 0: Automatic detection inhibited
1: Automatic detection enabled
p1250[0...n] Vdc controller proportional gain / Vdc_ctrl Kp
PM230
PM240
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 100.00 1.00
p1251[0...n] Vdc controller integral time / Vdc_ctrl Tn
PM230
PM240
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0 [ms] 10000 [ms] 0 [ms]
p1252[0...n] Vdc controller rate time / Vdc_ctrl t_rate
PM230
PM240
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0 [ms] 1000 [ms] 0 [ms]
p1254 Vdc_max controller automatic ON level detection / Vdc_max SenseOnLev
PM230 Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 1 0
p1254 Vdc_max controller automatic ON level detection / Vdc_max SenseOnLev
PM240 Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 1 1