Data Sheet for Product

19
Siemens
N5111
2021-12-14
Dimension drawing PM230 Power Module, IP20
H
B
T1
T2
Power Module PM230, IP20 with integrated line filter A
Dimensions (mm)
Clearances (mm)
2)
Frame size
H
1)
B
T1 with
IOP-2-BT
T1 with blanking
cover/
BOP-2
T2 without
cover
Waste heat
(top)
Cooling air
(bottom)
FSA
196
73
245
235
223
80
100
FSB
292
100
245
235
223
80
100
FSC
355
140
245
235
223
80
100
FSD
512
275
275
265
253
300
300
FSE
635
275
275
265
253
300
300
FSF
934
350
387
377
365
350
350
Power Module PM230, IP20 with external filter B
Dimensions (mm)
Clearances (mm)
2)
Frame size
H
1)
B
T1 with
IOP-2-BT
T1 with blanking
cover/
BOP-2
T2 without
cover
Waste heat
(top)
Cooling air
(bottom)
FSA
202
73
310
300
288
80
100
FSB
297
100
330
320
308
80
100
FSC
359
140
340
330
318
80
100
FSD
512
375
275
265
253
300
300
FSE
635
385
275
265
253
300
300
FSF
934
500
387
377
365
350
350
1)
When using a shield connection kit: FSA: + 80 mm; FSB: + 78 mm; FSC: + 77 mm; FSD, FSE, FSF: + 123 mm
2)
The Power Modules can be mounted side-by-side. For tolerance reasons, we recommend a lateral clearance of
approx. 1 mm.
For the frame sizes FSA FSC, the external filter B is pre-mounted on the back at the factory.
The frame sizes FSD FSF have a side filter that has to be mounted separately. The
dimensions above represent the total spatial requirements.