Operating Instructions
2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
78 List Manual, 04/2018, A5E33838102
Description: Sets the magnetizing inductance of the motor.
This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor
identification routine (p1910).
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: The parameter is not used for synchronous motors (p0300 = 2).
Description: The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the y coordinate (flux) for the 1st value pair of the characteristic.
Sets the first flux value of the saturation characteristic as a [%] referred to the rated motor flux (100 %).
Dependency: The following applies for the flux values:
p0362 < p0363 < p0364 < p0365
Refer to: p0366
Note: For induction motors, p0362 = 100 % corresponds to the rated motor flux.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
Description: The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the y coordinate (flux) for the 2nd value pair of the characteristic.
Sets the second flux value of the saturation characteristic as a [%] referred to the rated motor flux (100 %).
Dependency: The following applies for the flux values:
p0362 < p0363 < p0364 < p0365
Refer to: p0367
Note: For induction motors, p0363 = 100 % corresponds to the rated motor flux.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
p0360[0...n] Motor magnetizing inductance / Mot Lh
Access level: 3 Calculated: p0340 = 1,2 Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Unit group: - Unit selection: - Func. diagram: 6727
Min Max Factory setting
0.00000 [mH] 10000.00000 [mH] 0.00000 [mH]
p0362[0...n] Motor saturation characteristic flux 1 / Mot saturat.flux 1
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Unit group: - Unit selection: - Func. diagram: 6723, 6838
Min Max Factory setting
10.0 [%] 800.0 [%] 60.0 [%]
p0363[0...n] Motor saturation characteristic flux 2 / Mot saturat.flux 2
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Unit group: - Unit selection: - Func. diagram: 6723, 6838
Min Max Factory setting
10.0 [%] 800.0 [%] 85.0 [%]