Operating Instructions

Communication via PROFIBUS and PROFINET
3.8 Select telegram
Fieldbuses
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
79
3.8
Select telegram
Precondition
In the basic commissioning you have selected the control using PROFIBUS or PROFINET.
Telegrams for SINAMICS G120 inverters
The following table shows all of the telegrams for the G120 inverter.
In your inverter you have a list of telegrams that are available for your particular inverter.
Value p0922
1:
Standard telegram 1, PZD
-2/2 (factory setting, exceptions: CU250D and CU250S)
2:
Standard telegramm 2, PZD-4/4
3:
Standard telegram 3, PZD-5/9
4:
Standard telegram 4, PZD-6/14
7:
Standard telegram 7, PZD 2/2 (factory setting CU250D)
9:
Standard telegram 9, PZD
-10/5
20:
Standard telegram 20, PZD-2/6
110:
SIEMENS telegram 110, PZD-12/7
112:
SIEMENS telegram 111, PZD-12/12
350:
SIEMENS telegram 350, PZD-4/4
352:
SIEMENS telegram 352, PZD-6/6
353:
SIEMENS telegram 353, PZD-2/2, PKW-4/4
354:
SIEMENS telegram 354, PZD-6/6, PKW-4/4
999:
Free telegram
Extend telegram/change signal interconnection (Page 33)
(factory setting, CU250S)
For further information about telegrams:
PROFIDRIVE profile - Cyclic communication (Page 17).
PROFIsafe telegram selection
The settings for the PROFIsafe telegram selection are described in the "Safety Integrated"
Function Manual.