Operating Instructions

2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
276 List Manual, 04/2018, A5E33838102
Description: Sets the communication protocol for the field bus interface.
Value: 0: No protocol
4: CAN
Note: Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
Description: Sets the communication protocol for the field bus interface.
Value: 0: No protocol
3: PROFIBUS
Note: Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
Description: Sets the communication protocol for the field bus interface.
Value: 0: No protocol
1: USS
2: Modbus RTU
5: BACnet MS/TP
8: P1
Note: Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
Description: Sets the communication protocol for the field bus interface.
Value: 0: No protocol
7: PROFINET
10: EtherNet/IP
Note: Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
p2030 Field bus interface protocol selection / Field bus protocol
CU230P-2_CAN Access level: 1 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 9310
Min Max Factory setting
0 4 4
p2030 Field bus interface protocol selection / Field bus protocol
CU230P-2_DP Access level: 1 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 9310
Min Max Factory setting
0 3 3
p2030 Field bus interface protocol selection / Field bus protocol
CU230P-2_HVAC
CU230P-2_BT
Access level: 1 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 9310
Min Max Factory setting
0 8 0
p2030 Field bus interface protocol selection / Field bus protocol
CU230P-2_PN Access level: 1 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 9310
Min Max Factory setting
0 10 7