Operating Instructions
SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
231
2 Parameters
2.2 List of parameters
Description: Synchronous-reluctance motor:
Sets the ramp-up time of the current setpoint (p1610, p1611) when switching over from closed-loop controlled to
open-loop controlled operation.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Description: Sets the static torque setpoint for sensorless vector control in the low speed range.
This parameter is entered as a percentage referred to the rated motor torque (r0333).
For sensorless vector control, when the motor model is shut down, an absolute current is impressed. p1610
represents the maximum load that occurs at a constant setpoint speed.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Notice: p1610 should always be set to at least 10 % higher than the maximum steady-state load that can occur.
Note: For p1610 = 0%, a current setpoint is calculated that corresponds to the no-load case (ASM: rated magnetizing
current, RESM: no-load magnetizing current).
For p1610 = 100 %, a current setpoint is calculated that corresponds to the rated motor torque.
Negative values are converted into positive setpoints in the case of induction and permanent-magnet synchronous
motors as well as closed-loop controlled reluctance motors.
Description: Enters the dynamic torque setpoint for the low-speed range for sensorless vector control.
This parameter is entered as a percentage referred to the rated motor torque (r0333).
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Note: When accelerating and braking p1611 is added to p1610 and the resulting total torque is converted into an
appropriate current setpoint and controlled.
For pure accelerating torques, it is always favorable to use the torque precontrol of the speed controller (p1496).
p1601[0...n] Current injection ramp time / I_inject t_ramp
Access level: 3 Calculated: p0340 = 1,3 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6790
Min Max Factory setting
1 [ms] 10000 [ms] 20 [ms]
p1610[0...n] Torque setpoint static (sensorless) / M_set static
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6700, 6721, 6722,
6726
Min Max Factory setting
-200.0 [%] 200.0 [%] 50.0 [%]
p1611[0...n] Additional acceleration torque (sensorless) / M_suppl_accel
Access level: 2 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6700, 6721, 6722,
6726
Min Max Factory setting
0.0 [%] 200.0 [%] 30.0 [%]