Installation Instructions
Insert CU Remove CU
Screening methods
Fitting CU to PM
Line cable
Motor cable
Control cable
Shielding brackets
Wire
straps
Mains and Motor terminals
The Power Modules are fitted with detachable terminals. It can be removed
from the Power Module by pressing the release catch. The connectors are not
interchangeable.
Cable cross sections Tightening torques
FSA: 1.5 … 2.5 mm
2
16 … 14 AWG 0.5 Nm ( 4 lbf.in)
FSB: 1.5 … 6 mm
2
16 … 10 AWG 0.6 Nm ( 5 lbf.in)
FSC: 6 … 16 mm
2
10 … 6 AWG 1.5 Nm ( 13 lbf.in)
Dimensions IP20 Units FSA … FSC
Frame
size
Dimensions (mm)
Distances
(mm)
1)
Fixings
Drill pattern
(mm)
Height
Width
Depth
Max.
d
epth
w
ith CU
and OP
Air flow
Screw
Tightening
Torque
(Nm)
a
b
c
With
Shielding
Plate
Above
Below
FSA
196
276
73
165
250
80
100
M4
2.5
186
62.3
6
FSB
292
370
100
165
250
80
100
M4
2.5
281
80
6
FSC
355
432
140
165
250
80
100
M5
3.5
343
120
6
1)
The Power Modules can be mounted
side
-
by
-
side. Due to tolerance reasons, we recommend a lateral
distance of about 1 mm
.
Dimensions PT Units
Frame
size
Dimensions (mm)
Distances
(mm)
1)
Fixings
Drill pattern and cuto
Height
Width
Depth
Max.
d
epth
w
ith CU
and OP
Air flow
Screw
Tightening
Torque
(Nm)
a
b
c
d
With
Shielding
Plate
T1
T2
Above
Below
FSA
238
322
126
171
117.7
53.1
256
80
100
M5
3.5
103
106
88
198
FSB
345
430
154
171
117.7
53.1
256
80
100
M5
3.5
147.5
134
116
304
FSC
411
500
200
171
117.7
53.1
256
80
100
M5
3.5
123
174
156
365
1)
The Power Modules can be mounted side
-
by
-
side. Due to tolerance reasons, we recommend a lateral distance of about 1 mm
Cable length
Cable lengths
,
using
EMI Level
(Emission)
Screened cables, filtered units
(class A)
25
m
Second Environment, C2
1
)
Screened cables, filtered units (class A)
50 m
Second Environment, C
3
1)
Screened cables, unfiltered units
with external filter, class B
50 m
C1
1)
Screened cables, unfiltered units
with external filter, class B
plus output choke
1
50 m
C2
1)
Screened cables, filtered or unfiltered units
5
0 m
EMI Standard not fullfilled
Unscreened cables, filtered or unfiltered units
100 m
EMI Standard not fullfilled
1)
EMC compliant connection required
Getting Started
SINAMICS G120
Power Module PM230 FSA ... FSC
150 % for 3 s
110 % for 57 s
200 % for 3 s
150 % for 57 s
100 % for 240 s
100 % for 240 s
Permissible overload for operation
according „Low Overload“ (LO)
Overloads
Permissible overload for operation
according „High Overload“ (HO)
HO base load: 100 % HO power
100 % HO current
LO base load: 100 % LO power
100 % LO current
%
300240
1801200
100
200
60
t[s]
%
300240
1801200
100
150
60
t[s]
For United States / Canadian installations (UL/cUL): In order that the system is UL/cUL-compliant, use UL/cUL-certified J-type fuses. Use 75° C copper wire only.
Additional requirements for Canadian compliance:
Transient surge suppression must be installed on the line side of this equipment. We recommend a VZCA7 circuit breaker type rated at the following specifications:
480 V (phase to ground), 480 V (phase to phase), suitable for overvoltage category III, provides protection for a VPR maximum of 2 kV and type 1 or type 2 SPD application.
CAUTION - Cable cross-section for grounding: The earth cable must be at least as big as the power cables.
Declaration of Conformity
The Declaration of Conformity can be found at the following link:
http://support.automation.siemens.com/WW/view/en/30563514/134200
Siemens AG,
Frauenauracher Str. 80,
DE-91056 Erlangen
Issue 04/2014
Feature
Specification
Line voltage
3 AC 380 V … 480 V ± 10 % up to 200
0 m
(6600 ft)
installation altitude.
Output voltage
3 AC 0 V … input voltage * 0.9
5
Input frequency
50 Hz … 60 Hz, ± 3 Hz
Output frequency
0 Hz … 550 Hz, depending on the control mode
Power factor
0.
9
without line reactor
Inrush current
Less than rated input current
Pulse frequency (factory setting)
4 kHz. Can be increased in 2 kHz steps up to 16 kHz. Increasing the pulse frequencies leads to an output current reduction.
Electro
magnetic compatibility
Interference emission
:
The devices are suitable for second environment category C2 in accordance with IEC61800
-
3 if the following
conditions are fulfilled: The motor cable is a shielded cable with low capacitance and is not longer than 50 m. The pulse frequency does
not exceed 4 kHz, the current does not exceed the LO input value. For details, refer to the Hardware Installation Manual.
I
nterference immunity: The devices are suitable for second environment category C3
Braking methods
DC braking
Environmental rating
Built in units
(open type equipment)
: IP20,
Push through units: IP54 / UL type 12 when mounted on a flat surface of an enclosure
Motor overload protection
This equipment is capable of providing internal motor overload
protection according to UL508C. The protection level is 115
%, 230
% and
400 % full load current of the equipment. This is adjusted via parameter p0640 and assumes the equipment has had basic motor
commissioning for the motor used as described in the documentation.
LO Operation temperature
1)
-
1
0 °C … 40 °C (32 °F … 104 °F) without
current
derating / up to 60 °C (140 °F) with
current
derating
HO Operating temperature
1)
-
1
0 °C …
50 °C (
32
°F … 122 °F) without
current
derating / up to 60 °C (140 °F) with
current
derating
Storage temperature
-
40 °C … +70 °C (
-
40 °F … 158 °F)
Installation altitude above sea level
Up to 1000 m (3300 ft) without derating / Up to 4000 m (13000 ft) with derating
Humidity
< 95% RH
-
non
-
condensing
Environmental
condition
s
Suitable for environmental class 3C2 according to
IEC
60721
-
3
-
3 against damaging chemical substances
Pollution
For open type equipment according
to
pollution degree level 2. Protection against conductive pollution is required e.g. using an IP54
cabinet.
For enclosed type/Push Through equipment according pollution degree level 3.
Shock
Long
-
term storage in the transport packaging according to Class 1M2 of
IEC
60721
-
3
-
1 : Transport in the transport packaging according to
Class 2M3 of
IEC
60721
-
3
-
2
.
Operation according to
Class
3M2.
See
Hardware Installation Manual for detailed specifications.
Vibration
Long
-
term storage in the transport packaging according to Class 1M2 to
IEC
60721
-
3
-
1 : Transport in the transport packaging according to
Class 2M3 to IEC 60721-3-2. Operation according to Class 3M2. See Hardware Installation Manual for detailed specifications.
Line impedance
With
Uk 1 %, a line reactor must not be used
Short Circuit Current Rating
(SCCR)
Suitable for use on a circuit capable of delivering not more than 65 kA rms symetrical amperes; 480 Vac maximum when protecte
d by
Class J or R/C (JFHR2) semiconductor fuses only as stated
1) according to UL, operation with temperatures > 50 °C (122 °F) is not permitted at all.
The maximum temperature is determined by the component (Power Module, Control Unit or Operator panel) with the lowest maximum temperature
Specific Data
LO base load values HO base load values Rated
input
current
Frame
Size
Order No. *) Line fuses
Power Output
current
Power Output
current
Semi conductor fuse,
e.g. Siemens UL, J-typekW hp A kW hp A A
Built in units
0.37
0.50
1.3
0.25
0,34
0.9
1.3
FSA
6SL3210
-
1NE11
-
3_L1
3NE1 813
-
0
(16 A)
AJT2
2 A
0.55
0.75
1.7
0.37
0.50
1.3
1.8
FSA
6SL3210
-
1NE11
-
7_L1
3NE1 813
-
0
(16 A)
AJT4
4 A
0.75
1.00
2.2
0.55
0.75
1.7
2.3
FSA
6SL3210
-
1NE12
-
2_L1
3NE1 813
-
0
(16 A)
AJT4
4 A
1.10
1.50
3.1
0.75
1.00
2.2
3.2
FSA
6SL3210
-
1NE13
-
1_L1
3NE1 813
-
0
(16 A)
AJT6
6 A
1.50
2.00
4.1
1.10
1.50
3.1
4.2
FSA
6SL3210
-
1NE14
-
1_L1
3NE1 813
-
0
(16 A)
AJT6
10 A
2.20
3.00
5.9
1.50
2.00
4.1
6.1
F
SA
6SL3210
-
1NE15
-
8_L1
3NE1 813
-
0
(16 A)
AJT10
10 A
3.00
5
.00
7.7
2.20
3.00
5.9
8.0
FSA
6SL3210
-
1NE17
-
7_L1
3NE1 813
-
0
(16 A)
AJT10
1
0
A
4.00
5.00
10.2
3.00
5
.00
7.7
10.5
FSB
6SL3210
-
1NE21
-
0_L1
3NE1 813
-
0
(16 A)
AJT15
15
A
5.50
7.50
13.2
4
.00
5.00
10.2
13.
6
FSB
6SL3210
-
1NE21
-
3_L1
3NE1 814
-
0
(
20
A)
AJT20
20
A
7.50
10.00
18.0
5.50
7.50
13.2
18.6
FSB
6SL3210
-
1NE21
-
8_L1
3NE 18
15
-
0
(
2
5 A)
AJT25
25
A
11.00
15,00
26.0
7.50
10.00
18.0
26.9
FSC
6SL3210
-
1NE22
-
6_L1
3NE 1803
-
0
(
35
A)
AJT35
35
A
15.00
20.00
32.0
1
1.00
15.00
26.0
33.1
FSC
6SL3210
-
1NE23
-
2_L1
3NE 1817
-
0
(50 A)
AJT45
45
A
18.50
20.00
38.0
15.00
15.00
32.0
39.2
FSC
6SL3210
-
1NE23
-
8_L1
3NE 1817
-
0
(50 A)
AJT50
50 A
Push through units
3.00
5
.00
7.7
2.20
3.00
5.9
8.0
FSA
6SL3211
-
1NE17
-
7_L1
3NE1 813
-
0
(
16 A)
AJT10
10 A
7.50
10.00
18.0
5.50
7.50
13.2
18.6
FSB
6SL3211
-
1NE21
-
8_L1
3NE 1815
-
0
(25 A)
AJT25
25 A
18.50
20.00
38.0
15.00
15.00
32.0
39.2
FSC
6SL3211
-
1NE23
-
8_L1
3NE 1817
-
0
(50 A)
AJT50
50 A
*) _: A = filtered unit, U = unfiltered unit