Operating Instructions
SINAMICS G120 CU230P-2 Control Units
List Manual, 04/2018, A5E33838102
279
2 Parameters
2.2 List of parameters
Description: Sets the PROFIBUS ident number (PNO-ID).
SINAMICS can be operated with various identities on PROFIBUS. This allows the use of a PROFIBUS GSD that is
independent of the device (e.g. PROFIdrive VIK-NAMUR with ident number 3AA0 hex).
Value: 0: SINAMICS
1: VIK-NAMUR
Note: Every change only becomes effective after a POWER ON.
Description: Displays the PROFIdrive PZD state.
Dependency: Refer to: p2044
Note: When using the "setpoint failure" signal, the bus can be monitored and an application-specific response triggered
when the setpoint fails.
Description: Sets the delay time to initiate fault F01910 after a setpoint failure.
The time until the fault is initiated can be used by the application. This means that is is possible to respond to the
failure while the drive is still operational (e.g. emergency retraction).
Dependency: Refer to: r2043
Refer to: F01910
Description: Sets the additional monitoring time to monitor the process data received via PROFIBUS.
Enables short bus faults to be compensated.
If no process data is received within this time, then an appropriate message is output.
Dependency: Refer to: F01910
Note: For controller STOP, the additional monitoring time is not effective.
p2042 PROFIBUS Ident Number / PB ident No.
CU230P-2_DP Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0
r2043.0...2 BO: PROFIdrive PZD state / PD PZD state
CU230P-2_DP
CU230P-2_PN
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2410
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Setpoint failure Yes No -
02 Fieldbus operation Yes No -
p2044 PROFIdrive fault delay / PD fault delay
CU230P-2_DP
CU230P-2_PN
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2410
Min Max Factory setting
0 [s] 100 [s] 0 [s]
p2047 PROFIBUS additional monitoring time / PB suppl t_monit
CU230P-2_DP Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2410
Min Max Factory setting
0 [ms] 20000 [ms] 0 [ms]