Operating Instructions
Parameters
List of parameters
1-288
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Displays the smoothed actual value after the filter (PT1) of the technology controller
Description: Sets the upper limit for the actual value signal of the technology controller.
Dependency: Refer to: p2264, p2265, p2271
Refer to: F07426
Notice: If the actual value exceeds this upper limit, this results in fault F07426.
Description: Sets the lower limit for the actual value signal of the technology controller.
Dependency: Refer to: p2264, p2265, p2271
Refer to: F07426
Notice: If the actual value falls below this lower limit, this results in fault F07426.
Description: Sets the scaling factor for the actual value of the technology controller.
Dependency: Refer to: p2264, p2265, p2267, p2268, p2271
Note: For 100%, the actual value is not changed.
Description: Setting to use an arithmetic function for the actual value signal of the technology controller.
Value: 0: No function
1: Root function (root from x)
r2266 CO: Technology controller actual value after filter / Tec_ctr act aftFlt
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Units group: 9_1 Unit selection: p0595 Func. diagram: 7958
Min Max Factory setting
- [%] - [%] - [%]
p2267 Technology controller upper limit actual value / Tec_ctrl u_lim act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Units group: 9_1 Unit selection: p0595 Func. diagram: 7958
Min Max Factory setting
-200.00 [%] 200.00 [%] 100.00 [%]
p2268 Technology controller lower limit actual value / Tec_ctrl l_lim act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Units group: 9_1 Unit selection: p0595 Func. diagram: 7958
Min Max Factory setting
-200.00 [%] 200.00 [%] -100.00 [%]
p2269 Technology controller gain actual value / Tech_ctrl gain act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
0.00 [%] 500.00 [%] 100.00 [%]
p2270 Technology controller actual value function / Tec_ctr ActVal fct
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
0 3 0