Operating Instructions

2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
132 List Manual (LH9), 04/2014, A5E33838102B AA
Description: Setting and connector output for fixed speed setpoint 14.
Dependency: Refer to: p1020, p1021, p1022, p1023, r1024, r1197
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description: Setting and connector output for fixed speed setpoint 15.
Dependency: Refer to: p1020, p1021, p1022, p1023, r1024, r1197
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description: Sets the mode to select the fixed speed setpoint.
Value: 1: Direct
2: Binary
Note: Re p1016 = 1:
In this mode, the setpoint is entered via the fixed speed setpoints p1001 ... p1004.
Up to 16 different setpoints are obtained by adding the individual fixed speed setpoints.
Re p1016 = 2:
In this mode, the setpoint is entered via the fixed speed setpoints p1001 ... p1015.
Description: Sets the signal source for selecting the fixed speed setpoint.
Dependency: Selects the required fixed speed setpoint using p1020 ... p1023.
Displays the number of the actual fixed speed setpoint in r1197.
Sets the values for the fixed speed setpoints 1 ... 15 using p1001 ... p1015.
Refer to: p1021, p1022, p1023, r1197
Note: If a fixed speed setpoint has not been selected (p1020 ... p1023 = 0, r1197 = 0), then r1024 = 0 (setpoint = 0).
p1014[0...n] CO: Fixed speed setpoint 14 / n_set_fixed 14
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: p2000 Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: 3010
Min Max Factory setting
-210000.000 [rpm] 210000.000 [rpm] 0.000 [rpm]
p1015[0...n] CO: Fixed speed setpoint 15 / n_set_fixed 15
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: p2000 Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: 3010
Min Max Factory setting
-210000.000 [rpm] 210000.000 [rpm] 0.000 [rpm]
p1016 Fixed speed setpoint select mode / n_set_fix select
Access level: 2 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 3010, 3011
Min Max Factory setting
1 2 1
p1020[0...n] BI: Fixed speed setpoint selection Bit 0 / n_set_fixed Bit 0
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2505, 3010, 3011
Min Max Factory setting
- - 0