Operating Instructions

Parameter
Table 6-31 Basic setup of motorized potentiometer
Parameter Description Setting
p1035[0…n] BI: Motorized potentiometer
setpoint higher
Signal source to continuously increase the setpoint
The factory setting depends on the inverter.
Inverters with PROFIBUS or PROFINET interface:
[0] 2090.13
[1] 0
Inverters without PROFIBUS or PROFINET interface: 0
p1036[0…n] BI: Motorized potentiometer
setpoint lower
Signal source to continuously decrease the setpoint
The factory setting depends on the inverter.
Inverters with PROFIBUS or PROFINET interface:
[0] 2090.14
[1] 0
Inverters without PROFIBUS or PROFINET interface: 0
p1040[0…n] Motorized potentiometer
start value [rpm]
Start value that is effective when the motor is switched on.
Factory setting: 0 rpm
p1047 MOP ramp-up time [s] MOP ramp-up time
Factory setting: 10 s
p1048 MOP ramp-down time [s] MOP ramp-down time:
Factory setting: 10 s
r1050 Motorized potentiometer, set‐
point after the ramp-function
generator
Motorized potentiometer, setpoint after the ramp-function generator
p1070[0…n] CI: Main setpoint Signal source for the main setpoint
The factory setting depends on the Control Unit.
With PROFIBUS or PROFINET interface: [0] 2050[1]
Without PROFIBUS or PROFINET interface: [0] 755[0]
p1071[0…n] CI: Main setpoint scaling Signal source for scaling the main setpoint
Factory setting: 1
r1073 CO: Main setpoint active Displays the active main setpoint
p1075[0…n] CI: Supplementary setpoint Signal source for the supplementary setpoint
Factory setting: 0
p1076[0…n] CI: Supplementary setpoint
scaling
Signal source for scaling the supplementary setpoint
Factory setting: 0
Advanced commissioning
6.15 Setpoints
Converter with the CU230P-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257946B AF 265