Operating Instructions

List of Parameters
Parameters
1-41
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Displays the transformation angle.
Dependency: Refer to: r1778
Note: The transformation angle corresponds to the electrical commutation angle.
Description: Defines whether the motor and drive converter power settings (e.g. rated motor power - p0307) are expressed in
[kW] or [hp].
Depending on the selection, the rated motor frequency (p0310) is either set to 50 Hz or 60 Hz.
For p0100 = 0, 2, the following applies: The power factor (p0308) should be parameterized.
For p0100 = 1, the following applies: The efficiency (p0309) should be parameterized.
Value: 0: IEC-Motor (50 Hz, SI units)
1: NEMA motor (60 Hz, US units)
2: NEMA motor (60 Hz, SI units)
Dependency: If p0100 is changed, all of the rated motor parameters are reset. Only then are possible unit changeovers made.
The units of all motor parameters are changed that are involved in the selection of IEC or NEMA (e.g. r0206, p0307,
r0333, r0334, p0341, p0344, r1969).
Refer to: r0206, p0210, p0300, p0304, p0305, p0307, p0308, p0309, p0310, p0311, p0314, p0320, p0322, p0323,
p0335, r0337, p1800
Note: The parameter value is not reset when the factory setting is restored (p0010 = 30, p0970).
Description: Sets the number of Command Data Sets (CDS).
Dependency: Refer to: p0010, r3996
Notice: When the data sets are created, short-term communication interruptions may occur.
Note: It is possible to toggle between command parameters (BICO parameters) using this data set changeover.
Description: Sets the number of Drive Data Sets (DDS).
Dependency: Refer to: p0010, r3996
Notice: When the data sets are created, short-term communication interruptions may occur.
r0094 CO: Transformation angle / Transformat_angle
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2005 Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- [°] - [°] - [°]
p0100 IEC/NEMA mot stds / IEC/NEMA mot stds
Access level: 1 Calculated: - Data type: Integer16
Can be changed: C(1) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 2 0
p0170 Number of Command Data Sets (CDS) / CDS count
Access level: 2 Calculated: - Data type: Unsigned8
Can be changed: C(15) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
2 4 2
p0180 Number of Drive Data Sets (DDS) / DDS count
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: C(15) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
1 4 1