6.38 Line contactor control
A line contactor disconnects the inverter from the line supply, and therefore reduces the inverter
losses when the motor is not operational.
The inverter can control its own line contactor using a digital output. You must supply the
inverter with 24 V so that the line contactor control of the inverter also functions when
disconnected from the line supply.
Activate line contactor control
.
.
.
9
'&9
'21&
'212
'2&20
',
*1',1
9,1
U
%,S
S
U
Figure 6-72 Line contactor control via DO 2 with feedback signal via DI 3
In order that the inverter controls line contactor K1 using one of its own digital outputs, you
must interconnect the digital output with signal r0863.1 e.g. for DO 2: p0732 = 863.1.
Line contactor control with feedback signal
Interconnect p0860 with the signal of the corresponding digital input.
(QHUJL]HFRQWDFWRU
/LQHFRQWDFWRUIHHGEDFNVLJQDO
S S
W
W
'2
',
Figure 6-73 Line contactor control via DO 2 with feedback signal via DI 3
If the line contactor feedback signal is not available for longer than the time set in p0861, then
the inverter signals fault F07300.
$
%
&
Advanced commissioning
6.38 Line contactor control
Converter with the CU230P-2 Control Units